Description

Master FC400 is a frequency converter suitable for airport, military, and naval applications requiring a consistent 400 Hz output from either a 50 Hz or 60 Hz input. Adjustable 3-phase output voltage (200-215V).


Galvanic Isolation

Fully integrated output transformer guarantees the separation of the load from mains disturbances under all conditions. Takes incoming power at 50 or 60 Hz and converts it into a consistent and stable 400 Hz output.


Easy Installation And Maintenance

Master FC400 has a compact footprint, for example, a 125 kVA model requires just 0.86 m² floor space. All key components are easily accessed from the front of the UPS. With no need for side or rear clearance, you can install the UPS right up against the wall or in the corner.

Technical Specifications

INPUT

Voltage - 380 / 400 / 415 V three-phase

Voltage tolerance - 400 V ±20% @ full load

Frequency tolerance - 45 ÷ 65 Hz

Current distorsion - < 5% (HC Version)

Soft start - 0 - 100% in 120 sec. configurable


OUTPUT and INVERTER OUTPUT

Rated power - 60000 VA

Active power - 48000 W

Number phases - 3

Crest factor (Ipeak/Irms) - 3 : 1

Waveform - sinusoidal

Static stability - ± 1%

Dynamic stability - ± 5%

Frequency - 400 Hz

Voltage distortion with non-linear load - < 4%

Voltage distortion with linear load - < 3%

Overload - 110% for 60 min.; 125% for 10 min.; 150% for 1 min.


ENVIRONMENTAL

Altitude max - 6000 m

Color - Light gray RAL 7035

Remote controls - ESD and ON/OFF

Communication - Double RS232 + dry contacts + 2 slots for communications interface

Protection rating - IP20

AC/AC efficiency - up to 92%

Noise (at 1 m) - 65 dBA

Remote signals - dry contacts

Operating temperature - 0 °C - +40 °C (50 °C @ 75% load)

Relative humidity - 5-95% non-condensing

Standards - European directives: L V 2014/35/EU low voltage; EMC 2014/30/EU electromagnetic compatibility -- Directive and Standards: Safety IEC EN 62040-1; EMC IEC EN 62040-2; RoHS compliant -- Classification in accordance with IEC 62040-3 VFI - SS - 111


DATA

Weight - 480 kg

Dimensions (h w d) - 1900 x 800 x 800 mm

Related Products