top of page

SPS 16 ATS

Buy Now

658CB000001

Features

  • Redundant energy system with two input sources. 

  • Manual or automatic switching between power lines.

  • Extensive programming options for automatic switching.

  • LCD display + LEDS for operation and control. 

  • IEC output connections.

  • Easy installation on 19” rack.

  • USB, RS-232 and potential-free contact interfaces.

  • Parameter-setting and control software (for Windows OS).

  • Smart slot for SNMP card.

Email: sale@theupsteam.co.uk
Web Form

Enquire About This

Email: sale@theupsteam.co.uk
Web Form

Automatic Transfer Switch

Description

Salicru's SPS ATS series is an automatic switch between two single-phase AC power lines which, starting from two sine-wave current power lines, supplies output voltage to the load(s). The switching can be automatic or manual. The LCD display and status LEDs continually report the status of the device, working mode and values of the main measurements.

It has extensive communication possibilities through integrated USB, RS-232 and potential-free contact interfaces, or optional inclusion on an SNMP platform. In addition, by means of the parameter-setting software available, parameters such as delays, overload levels, voltage and frequency ranges, line sensitivity, potential-free contacts, etc., can be set.

Technical Specifications

INPUT

Rated voltage - 200 / 208 / 220 / 230 / 240 V

Voltage range - 150 ÷ 300 Vac

Rated frequency - 50 / 60 Hz


OUTPUT

Rated voltage - 200 / 208 / 220 / 230 / 240 V

Rated current (A) - 16 A

Performance - >99%


COMMUNICATION

Interface - RS-232, USB and potential-free contacts


INDICATIONS

Information - Source A, source B, failure, overload, alarm, audible alarm silencer

Monitoring software - Yes, for Windows OS

Type - LCD + LEDs

Values - Voltage, current, frequency, % load, error code


CONNECTIONS

Input - 2 x IEC C20

Output - 8x IEC C13 + 1x IEC C19


PROTECTION

Output - Overload


GENERAL

Operating temperature - 0ºC ÷ +40ºC

Relative humidity - Up to 95%, non-condensing

Maxium operating altitude - 2,400 masl


STANDARDS

Safety - IEC-60950-1

Electromagnetic compatibility (EMC) - EN-55022; EN-55024

Quality and environmental management - ISO 9001 & ISO 14001


DIMENSIONS

Depth (mm) - 275

Width (mm) - 438

Height (mm) - 44


WEIGHT

Weight (kg) - 4

Downloads