Description
The SLC X-TRA series is one of the most reliable, high-performance three-phase Uninterruptible Power Supply system (UPS) on the market, and provides protection and quality energy for a wide range of applications. Based on the Voltage and Frequency Independent (VFI) mode of operation, it has been developed using double conversion IGBT technology with DSP control, which gives considerable savings in the costs of operation and installation while it offers maximum protection for the connected loads.
This series has been conceived to offer the best guarantees in meeting customers' requirements and needs and has been designed in full respect of the most demanding environmental regulations.
The SLC X-TRA series features power range from 100 to 800 kVA in a very compact format for easier installation. Plus, the reliability of the system can be increased with the installation of several redundant units or it can grow in parallel based on the needs of the installation.
Technical Specifications
TECHNOLOGY - On-line, double conversion, DSP control
INPUT
Voltage - 3x380 / 3x400 / 3x415 V
Voltage range - +15% / -20% (@ 3 x 400 V)
Rated frequency - 50 / 60 Hz (45-65 Hz)
Frequency range - ±5 Hz or ±10Hz adjustable
Total harmonic distortion (THDi) - <3%
Power factor - >0.99
Protection - Internal fuses
OUTPUT
Power factor - 0.9
Voltage - 3x380 V / 3x400 V / 3x415 V (3F+N)
Voltage accuracy - ±1 %. Steady state -unbalanced load-: ±2 %. Dynamic state -load steps 20% - 100% - 20%: ±5 %.
Ripple - 1%
Total harmonic distortion (THDv) Non~linear load - <5%
Synchronised frequency - ±2 % others under request
Frequency - 50 / 60 Hz
Frequency accuracy (battery mode) - ±0.001 Hz
Synchronous speed - 1Hz/s
Eco-mode performance - >98%
Eco-mode performance - >98%
Admissible overloads - 125% for 10 min. / 150% for 1 min / 200% for 10 s />200% for 100ms
Crest factor - 3 a 1
Parallel - Through protocol CANBUS
MANUAL BYPASS
Type - Without interruption
100–300 kVA - Seriell
STATIC BYPASS
Type and activation criteria - Solid state, control by microprocessor
Voltage (V) - Three-phase 3 x 380 / 3 x 400 / 3 x 415 V (3Ph + N)
Transfer time - Nil
Transfer to bypass - Immediate for overloads of over 150%
Retransfer - Automatic after alarm disappearance
Voltage range - ±10% (Selectable between 1 ÷ 20%)
Input - Independent
Frequency - 50 / 60 Hz
Admissible overloads - 1000% for 1 cycle
RECTIFIER
Protection - Against transitory overvoltages
BATTERY
Protection - Against overvoltages and undervoltages
Battery type - Lead acid, sealed, maintenance free(1)
Charge type - IU in accordance with DIN41773
Recharge time - 4 hours, @ 80% of capacity
Charging voltage regulation - Batt-Watch
Battery test - Manual + Automatic
CHARGER
Temperature voltage compensation - 2,267 V/+25º C
COMMUNICATION
Ports - RS-232, USB, Emergency Power Off (EPO), Port for monitoring battery switch
Intelligent slot - 2 (One for SNMP and another one for MODBUS protocol)
Backlit LCD display - LCD + LED block diagram
INDICATIONS
Alarm - mains fault, scheduled maintenance necessary, input phase rotation not correct, common alarm, rectifier off, mbcb bus closed, rectifier failure, epo bus, wrong dc voltage, asymmetric load, batt in test, service required, bcb open, battery in diesel mode,
OTHER FUNCTIONS
Emergency stop (EPO) - Yes
GENERAL
Operating temperature - 0º C ÷ +40º C
Storage temperature - -10ºC ÷ +60ºC (with batteries) / -10ºC ÷ +70ºC (without batteries)
Relative humidity - Up to 95%, non-condensing
Maxium operating altitude - < 2,400 m.s.n.m.
Degree of protection - IP20
Acoustic noise at 1 metre - < 60 dB
Mean time between failures (MTBF) - 383000 hours with bypass
SYSTEMS
Maximum no. parallel systems - Yes, up to 6 units
IMPLEMENTATIONS
Nº Cabinets (Ups + BAT) - 1 + 1
STANDARDS
Safety - EN-IEC 62040-1
Electromagnetic compatibility (EMC) - EN-62040-2
Operation - VFI-SS-111 (EN-62040-3)
Quality and environmental management - ISO 9001 & ISO 14001
DIMENSIONS
Depth (mm) - 825
Width (mm) - 815
Height (mm) - 1670
WEIGHT
Weight (kg) - 630
(1) Ni-Cd under request.