top of page

SLC-20000-TWIN PRO2 B1

Buy Now

Email: sale@theupsteam.co.uk
Web Form

Enquire About The

Email: sale@theupsteam.co.uk
Web Form

SLC-20000-TWIN PRO2 B1

UPS

Description

Salicru's SLC TWIN PRO2 series UPS systems feature on-line double conversion technology, currently the most advanced for the protection of critical systems as it provides a fully stabilised and filtered sinusoidal supply voltage. The systems come in a tower format and are available in power ratings of 4, 5, 6, 8, 10, 15 and 20 kVA.

The Salicru SLC TWIN PRO2's output voltage is always single-phase, featuring a single-phase input of 4 to 20 kVA and a three-phase input of 8 to 20 kVA. All devices with single-phase input provide a unitary output power factor (1), the most optimum for systems and environments with high energy needs. Adaptability is another important feature thanks to the numerous operating modes available: On-line, Batteries, Eco-mode, Bypass, Frequency converter and Parallel redundant.

The possibilities of control and monitoring are varied: on the one hand, an LCD display + keypad for local operation of the device, and, on the other, various communication options (USB HID and RS-232 interfaces, and slot for SNMP, RS-485 and AS-400 cards) that enable the UPS to be integrated into standard or virtualised platforms for management, incident notification and remote maintenance.


(1) Except 15 and 20 kVA I / I models

Technical Specifications

TECHNOLOGY - On-line double conversion


FORMAT - Tower


INPUT / OUTPUT

Input / Output - I / I


INPUT

Voltage - 220 / 230 / 240 V

Voltage range - 110 ÷ 276 V

Rated frequency - 50 / 60 Hz

Frequency range - ±10%

Total harmonic distortion (THDi) - <5%

Power factor - ≥0.99


OUTPUT

Power factor - 0.9

Voltage - 208 / 220 / 230 / 240 V

Static accuracy - ±1%

Power (VA/W) - 20000 / 18000

Total harmonic distortion (THDv) Linerar load - ≤2%

Total harmonic distortion (THDv) Non~linear load - ≤5%

Synchronised frequency - ±4 Hz

Frequency accuracy (battery mode) - ±0.05 Hz

Total performance in On-line mode - 88% ÷ 90%

Admissible overloads - Up to 110% for 10 min; 130% for 1 min

Crest factor - 3 a 1

Parallel - Yes, up to 3 units(3)


MANUAL BYPASS

Type - No breaks


STATIC BYPASS

Type and activation criteria - Hybrid

Transfer time - Nil


BATTERY

Protection - Against power surges, undervoltages and alternating current components

Battery type - Pb-Ca sealed, AGM, maintenance-free

Charge type - I/U (constant current/constant voltage)

Recharge time - 9 hours to 90%


CHARGER

Temperature voltage compensation - Yes


COMMUNICATION

Ports - USB, RS-232 and relay

Intelligent slot - Yes, ready for SNMP / AS400 / RS485-Modbus

Monitoring software - Downloadable for Windows, Unix, Linux and Mac


OTHER FUNCTIONS

Cold start (start-up from batteries) - Yes


OPERATING MODES

Eco-mode - Yes

Frequency converter (CVCF) - Yes


GENERAL

Operating temperature - 0º C ÷ 40º C

Relative humidity - Up to 95%, non-condensing

Maxium operating altitude - 2,400 masl (power degradation up to 5,000 m)

Acoustic noise at 1 metre - < 60 dB


STANDARDS

Safety - EN-IEC 62040-1

Electromagnetic compatibility (EMC) - EN 62040-2 (C3)

Operation - VFI (EN-62040-3)

Quality and environmental management - ISO-9001 & ISO-14001


DIMENSIONS

Depth (mm) - 592

Width (mm) - 250

Height (mm) - 576


WEIGHT

Weight (kg) - 38


(1) Power reduction to 90% for 208 V input

(2) With 50% load

(3) Power reduction to 90%

(4) Power reduction to 60%

(5) Power reduction to 40%