Description
Salicru SLC TWIN RT3 series, rated from 1000 VA to 3000 VA, represents the perfect balance of features and performance: efficient operation as a double conversion UPS, optimised battery charging system, power density, high levels of connectivity (and the consequent immediacy of information), the flexibility offered by the multi-function output sockets (identified by colour), the automatic detection system for external battery modules, the beauty of its floating-prism design with high-quality finishes... in short, Salicru has gone the extra mile, in view of the critical nature of the systems this series is designed to protect.
As has become common practice for SLC TWIN RT devices, they come in a 2U rack format (easily converted to tower format) with adjustable display and keypad, ensuring easy adaptation to the needs of the installation.
The system’s extended backup requirements are amply met, thanks to the additional battery modules and the devices equipped with an improved 8A charger. Notably, the charger offers a “rest” mode during which no current is sent to the batteries, thereby reducing stress and extending the unit’s useful life.
Technical Specifications
TECHNOLOGY - On-line double-conversion
FORMAT - Convertible tower/rack with rotating display
INPUT
Rated voltage - 200/208/220/230/240 V
Voltage range - 10 ÷ 300 V(1)
Rated frequency - 50 / 60 Hz (auto-detection)
Frequency range - 50 ±5 Hz/60 ±6 Hz
Total harmonic distortion (THDi) - <5 %
OUTPUT
Power factor - 1
Rated voltage - 200/208/220/230/240 V(2)
Voltage accuracy - ±1%
Total harmonic distortion (THDv) - <1 % linear load / <5 % non-linear load
Synchronised frequency - 50 ±5 Hz/60 ±6 Hz
On-line performance - ≥89 ÷ 93 %
Eco-mode performance - ≥96 ÷ 97 %
Admissible overloads in battery mode - 105 ÷ 125 % for 2 min/125 ÷150 % for 10 s/>150 % for 500 ms
Admissible overloads in bypass mode - 105 ÷ 125 % for 10 min/125 ÷150 % for 5 min/>150 % for 500 ms
Admissible overloads in-line mode - 105 ÷ 125 % for 5 min/125 ÷150 % for 30 s/>150 % for 500 ms
Programmable sockets - Yes, for critical/non-critical loads (4/4)(3)
BATTERY
Battery type - Pb-Ca sealed, AGM, maintenance-free
Charge type - Smart charge with 3 modes
Recharge time - 3 hours to 90%
Maximum no. of EBMs - 4
CHARGER
Temperature voltage compensation - Yes
Charging current - 1.5 A (8 A for B1 devices)
COMMUNICATION
Ports - USB-HID/RS-232/RJ-45/HDMI for dongle wifi
Intelligent slot - For SNMP/AS400/MODBUS
Monitoring software - Software for Windows, Linux and Mac/app for iOS and Android/web portal
OTHER FUNCTIONS
Cold start (start-up from batteries) - Yes
Emergency stop (EPO) - Yes
OPERATING MODES
Frequency converter (CVCF) - Yes(4), operates with or without batteries
GENERAL
Operating temperature - 0º C ÷ +50º C(5)
Relative humidity - Up to 95%, non-condensing
Maxium operating altitude - 3.000 masl (6)
Acoustic noise at 1 metre - <45 dB ÷ <50 dB at full load/<36 dB ÷ <46 dB at 70% load
STANDARDS
Safety - EN IEC 62040-1
Electromagnetic compatibility (EMC) - EN IEC 62040-2(C2)
Operation - VFI-SS-31 (EN 62040-3)
Corporate cerification - ISO 9001, ISO 14001, ISO 45001
DIMENSIONS
Depth (mm) - 600
Width (mm) - 438
Height (mm) - 86
WEIGHT
Weight (kg) - 25,5
(1) 110 ÷ 160 V with linear derating of load at 50%
(2) Power derating at 80% for 200 V and 90% for 208 V
(3) The 3 kVA model has an additional fifth non-programmable IEC C19 output
(4) Power derating at 60%
(5) Power derating of 4% for each degree >40°C
(6) Power derating of 1% for each additional 100°m over 1000 MASL