Salicru’s SLC CUBE4 Uninterruptible Power Supplies (UPS) are the most cutting-edge security solution for all critical systems and sensitive loads. They have a Nimbus cloud connection as standard for equipment monitoring and remote management options, incident notification, equipment health monitoring and preventive maintenance.
With three-level on-line technology and quad-core DSP control, they are three-phase input/output systems that offer a range of first-class features, including unity power factor (kVA=kW), very low input distortion (THDi <3%) and performance in excess of 96% in On-line Mode and 99% in Eco Mode. They also boast parallel growth capacity or unlimited redundant security(1).
Across the entire range, the batteries are included in the same cabinet, meaning the floor area occupied is reduced by up to 40%. They are compatible with all types of battery (including lithium-ion) and incorporate the Batt-Watch battery care system to maximise battery life and availability.
(1) For models up to 20 kVA. Maximum of four devices in parallel.
Technical Specifications
TECHNOLOGY - On-line, double conversion, HF, DSP control
INPUT
Voltage - 3 × 380 / 3 × 400 / 3 × 415 V (3F + N)
Voltage range - 7.5÷20 kVA: 110÷300 V (F-N) / 30÷80 kVA: 115÷265 V (F-N)
Rated frequency - 50 / 60 Hz
Frequency range - 7.5÷20 kVA: 46÷54 Hz / 56÷64 Hz / 30÷80 kVA: 46÷64 Hz
Total harmonic distortion (THDi) - <3%
Power factor - 7.5÷20 kVA: ?0.99 / 30÷80 kVA: 1 from 10% load
Rectifier topology - Three-phase IGBT full wave, soft start, PFC, transformerless
OUTPUT
Power factor - 1
Voltage - 3 × 380 / 3 × 400 / 3 × 415 V (3F + N)
Dynamic accuracy - ±2%
Static accuracy - ±1%
Power (VA/W) - 60000 / 60000
Synchronised frequency - 50/60 Hz ±5 Hz (seleccionable)
Frequency - 50 / 60 Hz
Frequency accuracy (battery mode) - 50/60 Hz ±0,05%
Eco-mode performance - hasta 98,9%
Total performance in On-line mode - >96% (1)
Admissible overloads - 125% for 10 min / 150% for 60 s / >150% for 20 ms
Crest factor - 3 a 1
MANUAL BYPASS
Type - Uninterrupted
STATIC BYPASS
Type and activation criteria - Solid state
Transfer times in Smart Eco-mode (ms) - <10 ms
Transfer to bypass - Immediate, for overloads exceeding 150%
Retransfer - Automatic, after alarm deactivation
BATTERY
Battery type - Pb-Ca, VRLA, lead acid, gel, Ni-Cd, Li-Ion
Charging voltage regulation - Batt-Watch
COMMUNICATION
Ports - 1x RS232/RS485 + 1xUSB
Relay interface - 7.5÷20 kVA: 6 relays / 30÷80 kVA: 4 relays (programmable)
Intelligent slot - 1, for SNMP/ NIMBUS and relays
Monitoring software - CUBE4 Explorer
Backlit LCD display - 5” colour touch screen
GENERAL
Operating temperature - 0º C ÷ +40º C (2)
Relative humidity - Up to 95%, non-condensing
Maxium operating altitude - 2,400 masl (3)
Acoustic noise at 1 metre - 7.5÷10 kVA: <55 dB / 15÷20 kVA: <57 dB / 30÷40 kVA: <54 dB / 50÷80 kVA: <62 dB
SYSTEMS
Maximum no. parallel systems - No
STANDARDS
Safety - IEC/EN 62040-1
Electromagnetic compatibility (EMC) - IEC/EN 62040-2 C3
Operation - VFI-SS-111 (IEC/EN 62040-3)
Quality and environmental management - ISO 9001 & ISO 14001
DIMENSIONS
Depth (mm) - 920
Width (mm) - 560
Height (mm) - 1655
WEIGHT
Weight (kg) - 228
(1) According to model.
(2) Up to 55ºC with power derating.
(3) Power degradation for temperature altitudes, up to a maximum of 5,000 masl.