UPS

Description

The SLC X-TRA  series is one of the most reliable, high-performance three-phase Uninterruptible Power Supply system (UPS) on the market, and provides protection and quality energy for a wide range of applications. Based on the Voltage and Frequency Independent (VFI) mode of operation, it has been developed using double conversion IGBT technology with DSP control, which gives considerable savings in the costs of operation and installation while it offers maximum protection for the connected loads.

This series has been conceived to offer the best guarantees in meeting customers' requirements and needs and has been designed in full respect of the most demanding environmental regulations.

The SLC X-TRA  series features power range from 100 to 800 kVA in a very compact format for easier installation. Plus, the reliability of the system can be increased with the installation of several redundant units or it can grow in parallel based on the needs of the installation.

Technical Specifications

TECHNOLOGY - On-line, double conversion, DSP control


INPUT

Voltage - 3x380 / 3x400 / 3x415 V

Voltage range - +15% / -20% (@ 3 x 400 V)

Rated frequency - 50 / 60 Hz (45-65 Hz)

Frequency range - ±5 Hz or ±10Hz adjustable

Total harmonic distortion (THDi) - <3%

Power factor - >0.99

Protection - Internal fuses


OUTPUT

Power factor - 0.9

Voltage - 3x380 V / 3x400 V / 3x415 V (3F+N)

Voltage accuracy - ±1 %. Steady state -unbalanced load-: ±2 %. Dynamic state -load steps 20% - 100% - 20%: ±5 %.

Ripple - 1%

Total harmonic distortion (THDv) Non~linear load - <5%

Synchronised frequency - ±2 % others under request

Frequency - 50 / 60 Hz

Frequency accuracy (battery mode) - ±0.001 Hz

Synchronous speed - 1Hz/s

Eco-mode performance - >98%

Eco-mode performance - >98%

Admissible overloads - 125% for 10 min. / 150% for 1 min / 200% for 10 s />200% for 100ms

Crest factor - 3 a 1

Parallel  - Through protocol CANBUS


MANUAL BYPASS

Type - Without interruption

100–300 kVA - Seriell


STATIC BYPASS

Type and activation criteria - Solid state, control by microprocessor

Voltage (V) - Three-phase 3 x 380 / 3 x 400 / 3 x 415 V (3Ph + N)

Transfer time - Nil

Transfer to bypass - Immediate for overloads of over 150%

Retransfer - Automatic after alarm disappearance

Voltage range - ±10% (Selectable between 1 ÷ 20%)

Input - Independent

Frequency - 50 / 60 Hz

Admissible overloads - 1000% for 1 cycle


RECTIFIER

Protection - Against transitory overvoltages


BATTERY

Protection - Against overvoltages and undervoltages

Battery type - Lead acid, sealed, maintenance free(1)

Charge type - IU in accordance with DIN41773

Recharge time - 4 hours, @ 80% of capacity

Charging voltage regulation - Batt-Watch

Battery test - Manual + Automatic


CHARGER

Temperature voltage compensation - 2,267 V/+25º C


COMMUNICATION

Ports - RS-232, USB, Emergency Power Off (EPO), Port for monitoring battery switch

Intelligent slot - 2 (One for SNMP and another one for MODBUS protocol)

Backlit LCD display - LCD + LED block diagram


INDICATIONS

Alarm - mains fault, scheduled maintenance necessary, input phase rotation not correct, common alarm, rectifier off, mbcb bus closed, rectifier failure, epo bus, wrong dc voltage, asymmetric load, batt in test, service required, bcb open, battery in diesel mode,


OTHER FUNCTIONS

Emergency stop (EPO) - Yes


GENERAL

Operating temperature - 0º C ÷ +40º C

Storage temperature - -10ºC ÷ +60ºC (with batteries) / -10ºC ÷ +70ºC (without batteries)

Relative humidity - Up to 95%, non-condensing

Maxium operating altitude - < 2,400 m.s.n.m.

Degree of protection - IP20

Acoustic noise at 1 metre - < 60 dB

Mean time between failures (MTBF) - 383000 hours with bypass


SYSTEMS

Maximum no. parallel systems - Yes, up to 6 units


IMPLEMENTATIONS

Nº Cabinets (Ups + BAT) - 1 + 2


STANDARDS

Safety - EN-IEC 62040-1

Electromagnetic compatibility (EMC) - EN-62040-2

Operation - VFI-SS-111 (EN-62040-3)

Quality and environmental management - ISO 9001 & ISO 14001


DIMENSIONS

Depth (mm) - 950

Width (mm) - 2440

Height (mm) - 2020


WEIGHT

Weight (kg) - 2400


(1) Ni-Cd under request.